TES Power and Harmonics Analyzer PROVA-6830A
- Power Analysis for 3P3W, 1P2W, 3P4W, and 1P3W
- Active Power • True RMS value (V123 and I123) (W, KW, MW, GW)
- Reactive and seeming power (KVA, KVAR)
- Phase angle (), and Power Factor (PF)
- Energy (WH, KWH, KVARH, PFH)
- True RMS, Auto Range AC Current (0.04A to 6000A) and Voltage measurements.
- Able to assess IT standby power consumption up to the highest factory demand
- One screen displays 35 parameters (3P4W)
- Programmable PT and CT (1 to 600) (1 to 3000) Ratios
- Display of the Waveforms of Overlapping Voltage and Current
- Typical Demand (AD in W, KW, MW)
- Maximum Demand with Programmable Period (MD in KW, MW, KVA, and MVA)
- Analysis of harmonics up to the 99th order
- Waveform and 50 Harmonics Displayed on One Screen
- Waveform Peak Values Display (1024 Samples/Period)
- Total Harmonic Distortion Analysis (THD-F)
- Graphic Phasor Diagram for the Three-Phase System
- Capture 28 Transient Events with Programmable Threshold (%) (Time + Cycles)
- Transient events include DIP, SWELL, and OUTAGE.
- Unbalanced 3 Phase Voltage or Current (VUR, IUR)
- 3 Phase Unbalanced Voltage or Current (d0%, d2%)
- Calculated Neutral Line Unbalanced Current (In)
- 512K Memory with Interval Programming (Sampling time from 2 to 3000 seconds, 17,000 records for 3P4W system)
- Waveform, power parameters, and harmonic output on demand
- Large Backlit Dot Matrix LCD Display
- Software with an Optical Isolated RS-232C to USB Interface for use with a PC
- •Data logging timer and calendar built-in
- Size of Conductor:
- ■ Model 6801 (100A)
- 210mm (L) x 62mm (W) x 36mm (H), 200g, approx (Weight)
- ■ Model 6802 (1000A)
- 55mm(approx),64*24mm (bus bar)
- 600g, 244mm (L), 97mm (W), and 46mm (H) (Weight)
- ■ Model 3007 (3000A)
- 24in/610mm (Probe Length)
- 130mm (L), 80mm (W), 43mm (H), and 410g (Weight)
- ■ Model 3009 (1200A) (1200A)
- 18in/460mm (Probe Length)
- 130mm (L), 80mm (W), 43mm (H), and 390g (Weight)
- ■ Model 3006 (6000A)
- 130 x 80 x 43 mm, weighing 430 g (Weight)
PROVA-6830A + 6801 (100A)
Electrical Specifications: (23℃±5℃)
AC Watt
Range (0 to 100A) | Resolution | Accuracy of Readings |
5.0 – 999.9 W | 0.1W | ±1% ± 0.8W |
1.000 – 9.999 KW | 0.001 KW | ±1% ± 8W |
10.00 – 99.99 KW | 0.01 KW | ±1% ± 80W |
100.0 – 999.9 KW | 0.1 KW | ±1% ± 0.8KW |
1000 – 9999 KW | 1 KW | ±1% ± 8KW |
Range of CT (Current Transformer) Ratio: 1 to 600
AC Apparent Power (VA, from 0.000 VA to 9999 KVA): VA = V r.m.s. x A r.m.s
AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR): VAR = √(VA2 – W2)
AC Active Energy (mWH, WH, or KWH, from 0mWH to 999,999KWH): WH = W * Time (in hours)
AC Current (Auto range, TRMS, Overload Protection AC 200A)
Range | Resolution | Accuracy of Readings |
0.04 – 1 A | 0.1mA / 1mA | ±0.5% ± 0.05A |
0.4 – 10 A | 0.001A / 0.01A | ±0.5% ± 0.05A |
4 – 100 A | 0.01A / 0.1A | ±1.0% ± 0.5A |
AC Voltage (Auto range, TRMS, Overload Protection AC 800V)
Range | Resolution | Accuracy of Readings |
20.0 V – 500.0 V (Phase to Neutral) | 0.1 V | ±0.5% ± 5dgts |
20.0 V – 600.0 V (Phase to Phase) |
Range of VT (Voltage Transformer) Ratio: 1 to 3000
Harmonics of AC Voltage in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 49th | ±4% of reading ± 2.0% | |
50 – 99th | ±6% of reading ± 2.0% |
Harmonics of AC Voltage in Magnitude
Range | Resolution | Accuracy |
1 – 20th |
0.1V |
±2% ± 0.5V |
21 – 49th | ±4% of reading ± 0.5V | |
50 – 99th | ±6% of reading ± 0.5V |
Harmonics of AC Current in Percentage
Range | Resolution | Accuracy |
1 – 10th |
0.1% |
±0.2% of reading ± 1% |
11 – 20th | ±2% of reading ± 1% | |
21 – 50th (A range) | ±5% of reading ± 1% | |
21 – 50th (mA range) | ±10% of reading ± 1% | |
51 – 99th | ±35% of reading ± 1% |
Harmonics of AC Current in Magnitude
Range | Resolution | Accuracy |
1 – 10th |
0.1mA / 0.1A |
±0.2% of reading ±7dgts |
11 – 20th | ±2% of reading ±7dgts | |
21 – 50th (A range) | ±5% of reading ±7dgts | |
21 – 50th (mA range) | ±10% of reading ±7dgts | |
51 – 99th | ±35% of reading ±7dgts |
Power Factor (PF)
Range | Resolution | Accuracy |
0.00 – 1.00 | 0.01 | ± 0.04 |
Phase Angle (Φ)
Range | Resolution | Accuracy |
-180° to 180° | 0.1° | ± 1° |
Peak Value of ACV (peak value > 20V) or ACA (peak value > 10% of the range), VT=1
Range | Sampling Time | Accuracy of Reading |
50 Hz | 19μs | ± 5% ± 30 digits |
60 Hz | 16μs |
Crest Factor (C.F.) of ACV (peak value >20V)
or ACA (peak value > 10% of the range), VT=1
Range | Resolution | Accuracy of Readings |
1.00 – 99.99 | 0.01 | ± 5% ± 30 digits |
Frequency in AUTO mode
Range | Resolution | Accuracy |
45 – 65 Hz | 0.1Hz | ± 0.1Hz |
Total Harmonic Distortion (THD-F)
Range | Resolution | Accuracy |
0.0 – 20.0 % |
0.1% |
± 1% |
20.0 – 100% | ±3% of reading ± 5% | |
100 – 999.9% | ±10% of reading ±10% |
General Specifications: Indoors Use
PROVA 6830A Analyzer
Battery Type: | 1.5V SUM-3 x 8 |
External DC Input: | Use only power supply adapter
Model PHAPSA |
Display: | Dot Matrix LCD (240×128) with backlight |
LCD Update Rate: | 1 time / second |
Power Consumption: | 140mA (approx.) |
No. Of Samples: | 1024 samples / period |
Data Logging Files: | 85 |
Max. File Capacity: | 17474 records (3P4W, 3P3W)
26210 records (1P3W) 52420 records (1P2W) 4096 records (50 Harmonics / record) |
Sampling Time: | 2 to 3000 seconds for data logging |
Low battery Indication: | |
Overload Indication: | OL |
Operating Temperature: | -10°C to 50°C |
Operating Humidity: | less than 85% relative |
Storage Temperature: | -20°C to 60°C |
Storage Humidity: | less than 75% relative |
Dimension: | 257 (L) x 155 (W) x 57 (H) mm
10.1” (L) x 6.1” (W) x 2.3” (H) |
Weight: | 1160g (Batteries included) |
Accessories: | Probes (model 6801) x 3
Test leads (3 meter long) x 4 Alligator clips x 4 Carrying bag x 1 Users manual x 1 Batteries 1.5V x 8 AC power adapter x 1 |
PROVA 6801 Current Probes
Conductor Size: | 30mm (approx.) |
Cable Length: | 3000mm |
Range Selection: | Manual (1A, 10A, 100A) |
Battery: | powered by power analyzer |
Dimension: | 210mm (L) x 62mm (W) x 36mm (H)
8.3″ (L) x 2.5″ (W) x 1.4″ (H) |
Weight: | 200g |
PROVA-6830A + 6802 (1000A)
Electrical Specifications: (23℃±5℃)
AC Watt
Range (0 to 1000A) | Resolution | Accuracy of Readings |
5.0 – 999.9 W | 0.1W | ±1% ± 0.8W |
1.000 – 9.999 KW | 0.001 KW | ±1% ± 8W |
10.00 – 99.99 KW | 0.01 KW | ±1% ± 80W |
100.0 – 999.9 KW | 0.1 KW | ±1% ± 0.8KW |
1000 – 9999 KW | 1 KW | ±1% ± 8KW |
0.000 – 9.999MW | 0.001MW | ±1% ± 80KW |
Range of CT (Current Transformer) Ratio: 1 to 600
AC Apparent Power (VA, from 0.000 VA to 9999 KVA): VA = V r.m.s. x A r.m.s
AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR): VAR = √(VA2 – W2)
AC Active Energy (mWH, WH, or KWH, from 0mWH to 999,999KWH):
WH = W * Time (in hours)
AC Current (Auto range, TRMS, Overload Protection AC 2000A)
Range | Resolution | Accuracy of Readings |
10.00A | 0.001A/0.01A | – |
5A – 100.0A | 0.01A/0.1A | ±0.5% ± 0.5A |
50A – 1000.0 A | 0.1A/1 A | ±0.5% ± 5A |
AC Voltage (Auto range, TRMS, Overload Protection AC 800V)
Range | Resolution | Accuracy of Readings |
20.0 V – 500.0 V (Phase to Neutral) | 0.1 V | ±0.5% ± 5dgts |
20.0 V – 600.0 V (Phase to Phase) |
Range of VT (Voltage Transformer) Ratio: 1 to 3000
Harmonics of AC Voltage in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 49th | ±4% of reading ± 2.0% | |
50 – 99th | ±6% of reading ± 2.0% |
Harmonics of AC Voltage in Magnitude
Range | Resolution | Accuracy |
1 – 20th |
0.1V |
±2% ± 0.5V |
21 – 49th | ±4% of reading ± 0.5V | |
50 – 99th | ±6% of reading ± 0.5V |
Harmonics of AC Current in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1 % |
±2% |
21 – 49th | ±4% of reading ± 2.0% | |
50 – 99th | ±6% of reading ± 2.0% |
Harmonics of AC Current in Magnitude
Range | Resolution | Accuracy |
1 – 20th |
0.1A |
±2% of reading ±0.4A |
21 – 49th | ±4% of reading ±0.4A | |
50 – 99th | ±6% of reading ±0.4A |
Power Factor (PF)
Range | Resolution | Accuracy |
0.00 – 1.00 | 0.01 | ± 0.04 |
Phase Angle (Φ)
Range | Resolution | Accuracy |
-180° to 180° | 0.1° | ± 1° |
Peak Value of ACV (peak value > 20V) or ACA (peak value > 20A), VT=1
Range | Sampling Time | Accuracy of Reading |
50 Hz | 19μs | ± 5% ± 30 digits |
60 Hz | 16μs |
Crest Factor (C.F.) of ACV (peak value >20V) or ACA (peak value > 20A), VT=1
Range | Resolution | Accuracy of Readings |
1.00 – 99.99 | 0.01 | ± 5% ± 30 digits |
Frequency in AUTO mode
Range | Resolution | Accuracy |
45 – 65 Hz | 0.1Hz | ± 0.1Hz |
Total Harmonic Distortion (THD-F)
Range | Resolution | Accuracy |
0.0 – 20% |
0.1% |
± 2% |
20 – 100% | ± 6% of reading ± 1% | |
100 – 999.9 % | ± 10% of reading ± 1% |
General Specifications: Indoors Use
PROVA 6830A Analyzer
Battery Type: | 1.5V SUM-3 x 8 |
External DC Input: | Use only power supply adapter
Model PHAPSA |
Display: | Dot Matrix LCD (240×128) with backlight |
LCD Update Rate: | 1 time / second |
Power Consumption: | 140mA (approx.) |
No. Of Samples: | 1024 samples / period |
Data Logging Files: | 85 |
Max. File Capacity: | 17474 records (3P4W, 3P3W)
26210 records (1P3W) 52420 records (1P2W) 4096 records (50 Harmonics / record) |
Sampling Time: | 2 to 3000 seconds for data logging |
Low battery Indication: | |
Overload Indication: | OL |
Operating Temperature: | -10°C to 50°C |
Operating Humidity: | less than 85% relative |
Storage Temperature: | -20°C to 60°C |
Storage Humidity: | less than 75% relative |
Dimension: | 257 (L) x 155 (W) x 57 (H) mm
10.1” (L) x 6.1” (W) x 2.3” (H) |
Weight: | 1160g (Batteries included) |
Accessories: | Probes (model 6802) x 3
Test leads (3 meter long) x 4 Alligator clips x 4 Carrying bag x 1 Users manual x 1 Batteries 1.5V x 8 AC power adapter x 1 |
PROVA 6802 Current Probes
Conductor Size: | 55mm (approx.), 64 x 24mm (bus bar) |
Cable Length: | 3000mm |
Range Selection: | Manual (10A, 100A, 1000A) |
Battery: | powered by power analyzer |
Dimension: | 244mm (L) x 97mm (W) x 46mm (H)
9.6″ (L) x 3.8″ (W) x 1.8″ (H) |
Weight: | 600g |
PROVA-6830A + 3007 (3000A)
Electrical Specifications: (23℃±5℃)
AC Watt
Range
(0 to 3000A) |
Resolution | Accuracy of Readings | |
> 20 V and > 30A | < 20V or < 30A | ||
10.0 – 999.9 W | 0.1W |
±1% of range |
±2% of range |
1.000 – 9.999 KW | 0.001 KW | ||
10.00 – 99.99 KW | 0.01 KW | ||
100.0 – 999.9 KW | 0.1 KW | ||
1000 – 9999 KW | 1 KW |
Range of CT (Current Transformer) Ratio: 1 to 600
AC Apparent Power (VA, from 0.000 VA to 9999 KVA): VA = V r.m.s. x A r.m.s
AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR): VAR = √(VA2 – W2)
AC Active Energy (mWH, WH, or KWH, from 0mWH to 999,999KWH): WH = W * Time (in hours)
AC Current (Auto range, TRMS, Overload Protection AC 3000A)
Range | Resolution | Accuracy of Readings |
10.0 – 300.0A | 0.01A / 0.1A | ±1% of range |
300.0 – 3000A | 0.1A / 1A |
AC Voltage (Auto range, TRMS, Overload Protection AC 800V)
Range | Resolution | Accuracy of Readings |
20.0 V – 500.0 V (Phase to Neutral) | 0.1 V | ±0.5% ± 5dgts |
20.0 V – 600.0 V (Phase to Phase) |
Range of VT (Voltage Transformer) Ratio: 1 to 3000
Harmonics of AC Voltage in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 49th | ±4% of reading ± 2.0% | |
50 – 99th | ±6% of reading ± 2.0% |
Harmonics of AC Voltage in Magnitude
Range | Resolution | Accuracy |
1 – 20th |
0.1V |
±2% ± 0.5V |
21 – 49th | ±4% of reading ± 0.5V | |
50 – 99th | ±6% of reading ± 0.5V |
Peak Value of ACV (peak value > 20V) or ACA (peak value > 30A), VT=1
Range | Sampling Time | Accuracy of Reading |
50 Hz | 19μs | ± 5% ± 30 digits |
60 Hz | 16μs |
Crest Factor (C.F.) of ACV (peak value >20V) or ACA (peak value > 30A), VT=1
Range | Resolution | Accuracy of Readings |
1.00 – 99.99 | 0.01 | ± 5% ± 30 digits |
Harmonics of AC Current in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 50th | ±6% | |
51 – 99th | ±10% |
Harmonics of AC Current in Magnitude
(1 to 99th order, min. current at the 50 or 60 Hz, True RMS < 300A)
Range (0 – 300A) | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% of reading ± 4A |
21 – 50th | ±4% of reading ± 4A | |
51 – 99th | ±6% of reading ± 4A |
(1 to 99th order, min. current at the 50 or 60 Hz, 3000A > True RMS > 300A)
Range (300–3000A) | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% of reading ± 40A |
21 – 50th | ±4% of reading ± 40A | |
51 – 99th | ±6% of reading ± 40A |
Power Factor (PF)
Range | Resolution | Accuracy | |
> 20V and > 30A | < 20V or < 30A | ||
0.000 – 1.000 | 0.001 | ± 0.04 | ±0.1 |
Phase Angle (Φ, V > 20V, A > 30A)
Range | Resolution | Accuracy |
-180° to 180° | 0.1° | ± 2° |
0° to 360° |
Frequency of ACV (RMS value > 10V) or ACA (RMS value > 30A)
Range | Resolution | Accuracy |
45 – 65 Hz | 0.1 Hz | ± 0.2Hz |
Total Harmonic Distortion (THD-F)
Range | Resolution | Accuracy |
0.0 – 20% |
0.1% |
± 2% |
20 – 100% | ± 6% of reading ± 5% | |
100 – 999.9 % | ± 10% of reading ± 10% |
General Specifications: Indoors Use
PROVA 6830A Analyzer
Battery Type: | 1.5V SUM-3 x 8 |
External DC Input: | Use only power supply adapter Model PHAPSA |
Display: | Dot Matrix LCD (240×128) with backlight |
LCD Update Rate: | 1 time / second |
Power Consumption: | 140mA (approx.) |
No. Of Samples: | 1024 samples / period |
Data Logging Files: | 85 |
Max. File Capacity: | 17474 records (3P4W, 3P3W)
26210 records (1P3W) 52420 records (1P2W) 4096 records (50 Harmonics / record) |
Sampling Time: | 2 to 3000 seconds for data logging |
Low battery Indication: | |
Overload Indication: | OL |
Operating Temperature: | -10°C to 50°C |
Operating Humidity: | less than 85% relative |
Storage Temperature: | -20°C to 60°C |
Storage Humidity: | less than 75% relative |
Dimension: | 257 (L) x 155 (W) x 57 (H) mm
10.1” (L) x 6.1” (W) x 2.3” (H) |
Weight: | 1160g (Batteries included) |
Accessories: | Probes (model 3007) x 3
Test leads (3 meter long) x 4 Alligator clips x 4, Carrying bag x 1 Users manual x 1, Batteries 1.5V x 8 AC power adapter x 1, Software CD x 1 |
AFLEX 3007 Flexible Current Probes
Probe Length: ( 3007-24) | 24 in / 610 mm |
Minimum Bending Diameter: | 35mm |
Connector Diameter: | 23mm |
Cable Diameter: | 14mm |
Cable Length from Probe to Box: | 1700mm |
Cable Length from Box to Output: | 1700mm |
Range Selection: | Manual (300A, 3000A) |
Battery: | powered by power analyzer |
Dimension (Box): | 130mm(L) x 80mm(W)x 43mm(H)
5.1”(L) x 3.1”(W) x 1.7”(H) |
Weight: | 410g |
PROVA-6830A + 3009 (1200A)
Electrical Specifications: (23℃±5℃)
AC Watt
Range
(0 to 1200A) |
Resolution | Accuracy of Readings | |
> 20 V and > 30A | < 20V or < 30A | ||
10.0 – 999.9 W | 0.1W |
±1% of range |
±2% of range |
1.000 – 9.999 KW | 0.001 KW | ||
10.00 – 99.99 KW | 0.01 KW | ||
100.0 – 999.9 KW | 0.1 KW | ||
1000 – 9999 KW | 1 KW |
Range of CT (Current Transformer) Ratio: 1 to 600
AC Apparent Power (VA, from 0.000 VA to 9999 KVA): VA = V r.m.s. x A r.m.s
AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR): VAR = √(VA2 – W2)
AC Active Energy (mWH, WH, or KWH, from 0mWH to 999,999KWH): WH = W * Time (in hours)
AC Current (Auto range, TRMS, Overload Protection AC 1200A)
Range | Resolution | Accuracy of Readings |
6.0 – 120.0A | 0.01A / 0.1A | ±1% of range |
120.0 – 1200A | 0.1A / 1A |
AC Voltage (Auto range, TRMS, Overload Protection AC 800V)
Range | Resolution | Accuracy of Readings |
20.0 V – 500.0 V (Phase to Neutral) | 0.1 V | ±0.5% ± 5dgts |
20.0 V – 600.0 V (Phase to Phase) |
Range of VT (Voltage Transformer) Ratio: 1 to 3000
Harmonics of AC Voltage in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 49th | ±4% of reading ± 2.0% | |
50 – 99th | ±6% of reading ± 2.0% |
Harmonics of AC Voltage in Magnitude
Range | Resolution | Accuracy |
1 – 20th |
0.1V |
±2% ± 0.5V |
21 – 49th | ±4% of reading ± 0.5V | |
50 – 99th | ±6% of reading ± 0.5V |
Peak Value of ACV (peak value > 20V) or ACA (peak value > 30A), VT=1
Range | Sampling Time | Accuracy of Reading |
50 Hz | 19μs | ± 5% ± 30 digits |
60 Hz | 16μs |
Crest Factor (C.F.) of ACV (peak value >20V) or ACA (peak value > 30A), VT=1
Range | Resolution | Accuracy of Readings |
1.00 – 99.99 | 0.01 | ± 5% ± 30 digits |
Harmonics of AC Current in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 50th | ±6% | |
51 – 99th | ±10% |
Harmonics of AC Current in Magnitude
(1 to 99th order, min. current at the 50 or 60 Hz, True RMS < 120A)
Range (0 – 120A) | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% of reading ± 4A |
21 – 50th | ±4% of reading ± 4A | |
51 – 99th | ±6% of reading ± 4A |
(1 to 99th order, min. current at the 50 or 60 Hz, 1200A > True RMS > 120A)
Range (120–1200A) | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% of reading ± 40A |
21 – 50th | ±4% of reading ± 40A | |
51 – 99th | ±6% of reading ± 40A |
Power Factor (PF)
Range | Resolution | Accuracy | |
> 20V and > 30A | < 20V or < 30A | ||
0.000 – 1.000 | 0.001 | ± 0.04 | ±0.1 |
Phase Angle (Φ, V > 20V, A > 30A)
Range | Resolution | Accuracy |
-180° to 180° | 0.1° | ± 2° |
0° to 360° |
Frequency of ACV (RMS value > 10V) or ACA (RMS value > 30A)
Range | Resolution | Accuracy |
45 – 65 Hz | 0.1 Hz | ± 0.2Hz |
Total Harmonic Distortion (THD-F)
Range | Resolution | Accuracy |
0.0 – 20% |
0.1% |
± 2% |
20 – 100% | ± 6% of reading ± 5% | |
100 – 999.9 % | ± 10% of reading ± 10% |
General Specifications: Indoors Use
PROVA 6830A Analyzer
Battery Type: | 1.5V SUM-3 x 8 |
External DC Input: | Use only power supply adapter Model PHAPSA |
Display: | Dot Matrix LCD (240×128) with backlight |
LCD Update Rate: | 1 time / second |
Power Consumption: | 140mA (approx.) |
No. Of Samples: | 1024 samples / period |
Data Logging Files: | 85 |
Max. File Capacity: | 17474 records (3P4W, 3P3W)
26210 records (1P3W) 52420 records (1P2W) 4096 records (50 Harmonics / record) |
Sampling Time: | 2 to 3000 seconds for data logging |
Low battery Indication: | |
Overload Indication: | OL |
Operating Temperature: | -10°C to 50°C |
Operating Humidity: | less than 85% relative |
Storage Temperature: | -20°C to 60°C |
Storage Humidity: | less than 75% relative |
Dimension: | 257 (L) x 155 (W) x 57 (H) mm
10.1” (L) x 6.1” (W) x 2.3” (H) |
Weight: | 1160g (Batteries included) |
Accessories: | Probes (model 3009) x 3
Test leads (3 meter long) x 4 Alligator clips x 4, Carrying bag x 1 Users manual x 1, Batteries 1.5V x 8 AC power adapter x 1, Software CD x 1 |
AFLEX 3009 Flexible Current Probes
Probe Length: ( 3009-18) | 18 in / 460 mm |
Minimum Bending Diameter: | 35mm |
Connector Diameter: | 23mm |
Cable Diameter: | 14mm |
Cable Length from Probe to Box: | 1700mm |
Cable Length from Box to Output: | 1700mm |
Range Selection: | Manual (120A, 1200A) |
Battery: | powered by power analyzer |
Dimension (Box): | 130mm(L) x 80mm(W)x 43mm(H)
5.1”(L) x 3.1”(W) x 1.7”(H) |
Weight: | 390g |
PROVA-6830A + 3006 (6000A)
Electrical Specifications: (23℃±5℃)
AC Watt
Range(0 to 6000A) | Resolution | Accuracy of Readings | |
> 20 V and > 60A | < 20V or < 60A | ||
10.0 – 999.9 W | 0.2W | ±1% of range | ±2% of range |
1.000 – 9.999 KW | 0.002 KW | ||
10.00 – 99.99 KW | 0.02 KW | ||
100.0 – 999.9 KW | 0.2 KW | ||
1000 – 9999 KW | 2 KW |
Range of VT (Voltage Transformer) Ratio: 1 to 3000
AC Apparent Power (VA, from 0.000 VA to 9999 KVA): VA = V r.m.s. x A r.m.s
AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR): VAR = √(VA2 – W2)
AC Active Energy (mWH, WH, or KWH, from 0mWH to 999,999KWH): WH = W * Time (in hours)
AC Current (Auto range, TRMS, Overload Protection AC 6000A)
Range | Resolution | Accuracy of Readings |
20.0 – 600.0A | 0.2A | ±1% of range |
600.0 – 6000A | 0.2A / 2A |
AC Voltage (Auto range, TRMS, Overload Protection AC 800V)
Range | Resolution | Accuracy of Readings |
20.0 V – 500.0 V (Phase to Neutral) | 0.1 V | ±0.5% ± 5dgts |
20.0 V – 600.0 V (Phase to Phase) |
Range of VT (Voltage Transformer) Ratio: 1 to 3000
Harmonics of AC Voltage in Percentage
Range | Resolution | Accuracy |
1 – 20th | 0.1% | ±2% |
21 – 49th | ±4% of reading ± 2.0% | |
50 – 99th | ±6% of reading ± 2.0% |
Harmonics of AC Voltage in Magnitude
Range | Resolution | Accuracy |
1 – 20th |
0.1V |
±2% ± 0.5V |
21 – 49th | ±4% of reading ± 0.5V | |
50 – 99th | ±6% of reading ± 0.5V |
Peak Value of ACV (peak value > 20V) or ACA (peak value > 60A), VT=1
Range | Sampling Time | Accuracy of Reading |
50 Hz | 19μs | ± 5% ± 30 digits |
60 Hz | 16μs |
Crest Factor (C.F.) of ACV (peak value >20V) or ACA (RMS value > 60A), VT=1
Range | Resolution | Accuracy of Readings |
1.00 – 99.99 | 0.01 | ± 5% ± 60 digits |
Harmonics of AC Current in Percentage
Range | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% |
21 – 50th | ±6% | |
51 – 99th | ±10% |
Harmonics of AC Current in Magnitude
(1 to 99th order, min. current at the 50 or 60 Hz, True RMS < 600A)
Range (0 – 600A) | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% of reading ± 8A |
21 – 50th | ±4% of reading ± 8A | |
51 – 99th | ±6% of reading ± 8A |
(1 to 99th order, min. current at the 50 or 60 Hz, 6000A > True RMS > 600A)
Range (600–6000A) | Resolution | Accuracy |
1 – 20th |
0.1% |
±2% of reading ± 80A |
21 – 50th | ±4% of reading ± 80A | |
51 – 99th | ±6% of reading ± 80A |
Power Factor (PF)
Range | Resolution | Accuracy | |
> 20V and > 60A | < 20V or < 60A | ||
0.000 – 1.000 | 0.001 | ± 0.04 | ±0.1 |
Phase Angle (Φ, V > 20V, A > 60A)
Range | Resolution | Accuracy |
-180° to 180° | 0.1° | ± 2° |
0° to 360° |
Frequency of ACV (RMS value > 10V) or ACA (RMS value > 60A)
Range | Resolution | Accuracy |
45 – 65 Hz | 0.1 Hz | ± 0.2Hz |
Total Harmonic Distortion (THD-F)
Range | Resolution | Accuracy |
0.0 – 20% |
0.1% |
± 2% |
20 – 100% | ± 6% of reading ± 5% | |
100 – 999.9 % | ± 10% of reading ± 10% |
General Specifications: Indoors Use
PROVA 6830A Analyzer
Battery Type: | 1.5V SUM-3 x 8 |
External DC Input: | Use only power supply adapter Model PHAPSA |
Display: | Dot Matrix LCD (240×128) with backlight |
LCD Update Rate: | 1 time / second |
Power Consumption: | 140mA (approx.) |
No. Of Samples: | 1024 samples / period |
Data Logging Files: | 85 |
Max. File Capacity: | 17474 records (3P4W, 3P3W)
26210 records (1P3W) 52420 records (1P2W) 4096 records (50 Harmonics / record) |
Sampling Time: | 2 to 3000 seconds for data logging |
Low battery Indication: | |
Overload Indication: | OL |
Operating Temperature: | -10°C to 50°C |
Operating Humidity: | less than 85% relative |
Storage Temperature: | -20°C to 60°C |
Storage Humidity: | less than 75% relative |
Dimension: | 257 (L) x 155 (W) x 57 (H) mm
10.1” (L) x 6.1” (W) x 2.3” (H) |
Weight: | 1160g (Batteries included) |
Accessories: | Probes (model 3006) x 3
Test leads (3 meter long) x 4 Alligator clips x 4, Carrying bag x 1 Users manual x 1, Batteries 1.5V x 8 AC power adapter x 1, Software CD x 1 |
AFLEX 3006 Flexible Current Probes
Probe Length: ( 3006-36 ) | 36 in / 920 mm |
Minimum Bending Diameter: | 35mm |
Connector Diameter: | 23mm |
Cable Diameter: | 14mm |
Cable Length from Probe to Box: | 1700mm |
Cable Length from Box to Output: | 1700mm |
Range Selection: | Manual (600A, 6000A) |
Battery: | powered by power analyzer |
Dimension (Box): | 130mm(L) x 80mm(W)x 43mm(H)
5.1”(L) x 3.1”(W) x 1.7”(H) |
Weight: | 430g |